ASD ISM 1719 Colour code for TOP SECRET cables
What it says
TOP SECRET cables are coloured red.
Quoted as published. Everything else on this page is written by Control Stack.
In plain English
TOP SECRET cables must be coloured red; a TOP SECRET cable in any other colour must be banded and labelled under ISM-1216 but does not meet this control until replaced.
TOP SECRET cables must be coloured red, whatever the cable type, and the control names no other colour. ISM-0926 keeps red off non-classified, OFFICIAL: Sensitive and PROTECTED cables. Red alone does not prove a cable is TOP SECRET, because Australian Standards set red for some building cabling such as fire control, which carries purpose labels under ISM-1639. A TOP SECRET cable in another colour stays non-conformant until replaced, and ISM-1216 requires red bands around it and labels at inspection points. ISM-1721 sets red for TOP SECRET wall outlet boxes.
Free. Save your status, tasks and notes.
Why it matters
Red helps installers and inspectors pick out TOP SECRET cables. A TOP SECRET cable in another colour looks like a cable for a lower classified system, so it can be patched or bundled with those cables, or passed over during an inspection.
How to implement
Specify red for every TOP SECRET cable.
Put it in work orders and contractor instructions for each cable type used. The control gives no colour code, so keep a physical sample for installers to match, and avoid a shade that could pass for the salmon pink ISM-1718 sets for SECRET cables.
Confirm supply before work starts.
Check that the supplier can provide red in each cable type and length you need. If it cannot, a cable in another colour is still non-conformant, and ISM-1216 requires red bands around it and labels at inspection points, the places where it can be viewed and inspected.
Find TOP SECRET cables in any other colour.
Start at TOP SECRET patch panels (ISM-0213), cabinets (ISM-1100) and wall outlet boxes (ISM-1105), and follow each run through TOP SECRET areas, where ISM-1119 requires its entire length to be inspectable. Compare with the cable register (ISM-0208). Apply ISM-1216 to each cable until you replace it, and keep its recorded colour correct.
Tell TOP SECRET cables apart from other red cables.
Where red fire control or other building cables run nearby, make sure they carry purpose labels (ISM-1639), so neither is taken for the other. Do not recolour those cables, because ISM-0181 requires cabling to follow the relevant Australian Standards.
Keep it running
Keep red cable on hand for repairs, so urgent work does not bring in another colour. Any change to TOP SECRET cabling, a new supplier, or building works adding red fire control cables nearby should prompt another check.
Evidence and audit
- Check 1 of 2What an auditor asks for
Ask for
Cables traced from TOP SECRET patch panels, cabinets and wall outlet boxes, picked on site rather than from the cable register.
Look at
The colour of each cable along its route.
Good evidence
Every traced cable is red. A cable in another colour does not meet this control even when banded, so it is reported as non-conformant and its bands and labels are checked against ISM-1216. A recorded plan to replace a cable does not count.
- Check 2 of 2What an auditor asks for
Ask for
The cable register (ISM-0208) filtered to TOP SECRET cables, with a sample of those cables seen on site.
Look at
The colour recorded for each cable, and whether the sampled cables match it.
Good evidence
Each TOP SECRET cable is recorded as red, and each sampled cable is the colour the register shows. Any other recorded colour is reported as non-conformant, and its bands and labels are checked on site (ISM-1216).
Mappings
Closest match in ISO/IEC 27001: A.7.12, Cabling security, which this control partially meets.
ISO/IEC 27001: 2 mappings
This control partially meets A.7.12.
ISM-1719 requires TOP SECRET cables to be coloured red so they can be rapidly and reliably identified as highly sensitive cabling. This supports Annex A 7.12 because clear visual identification assists correct physical handling and routing (e.g. segregation, heightened protection, prompt detection of misplacement), which reduces the likelihood of inadvertent exposure, interference or damage to sensitive cabling. Annex A 7.12 is about protecting cabling from interception/interference/damage overall, while ISM-1719 is a specific identification mechanism for one classification level rather than a complete cabling protection control.
This control supports A.5.12.
ISM-1719 requires a concrete classification-driven marking rule: TOP SECRET cables are coloured red to signal their sensitivity. This supports Annex A 5.12 because an effective information classification policy and practice typically needs implementable handling and identification conventions for classified assets, and ISM-1719 is one such convention applied to a specific asset type (cabling). Annex A 5.12 sets the organisational approach to classification across information and associated assets, whereas ISM-1719 does not define classification criteria and only prescribes one physical marking outcome.
Mappings show how controls relate across frameworks. They do not imply full equivalence or certification.